Outdated Information
This online document might be outdated. Please see the LucidControl USB Analog Input Module PDF documentation instead.
4 Specification
This section contains the technical specification of the LucidControl Analog Input USB Module
| Parameter | Condition | Value | |
|---|---|---|---|
| Inputs | |||
| No. of Input Channels | 4 | ||
| Inputs – Electrical Characteristics | |||
| Measurement Method | Analog to Digital Conversion | ||
| Voltage Range | AI4-05 | 0 ~ 5 V | |
| AI4-10 | 0 ~ 10 V | ||
| AI4-24 | 0 ~ 24 V | ||
| Resolution | 14 bit | ||
| Accuracy | typ. ±0.25 % of full scale range |
||
| Max. Measurement Error | ±5 LSB | ||
| Input Resistance | 100 kΩ | ||
| Inputs – Timing Characteristic | |||
| Scan Interval | TScan | 50 ms ≤ TScan ≤ 10 s | |
| Module – Host Interface | |||
| USB | 2.0 Full Speed CDC Profile | ||
| Power Supply | USB Bus Powered with +5V No additional Power Supply needed |
||
| Maximum Rated Current | 40 mA | ||
| Module – Environment | |||
| Temperature | Storage | -20 °C … +70 °C | |
| Operation | 0 °C … +55 °C | ||
| Humidity | <85 % RH, non-condensing | ||
| Module – Housing | |||
| Dimensions L x W x H | 90 x 54 x 62 mm | ||
| Weight (in total) | 120 g | ||
| Assembly | Rail-Mount (EN 50022, TS35) | ||
| Protection Class (DIN 40050) | IP20 | ||
| Module – Indicators | |||
| Operation and Status Indicator | |||
| Communication Indicator | |||
| Software | |||
| Supported Operating Systems | Windows® XP, Windows® Vista, Windows® 7 Ubuntu, Debian, Raspbian |
||
| Application Programming Interface (API) | Console / Terminal Application Java and Python |
||
| Previous | Top | Next |
|---|---|---|
| 3 Module Operation | LucidControl Analog Input USB Module Content | 5 Order Information |